Ventilation is hereby defined as the providing and maintaining in rooms and spaces, by natural or mechanical means, air conditions which will protect the health and comfort of the occupants thereof.
The ventilating requirements shall be based on the purposes for which the rooms are used, regardless of the class of building or structure in which it is located. The method of producing ventilation and the quantities of air to be supplied and exhausted by mechanical ventilating systems stated in the tables in Section 13-176-070 are the minimums permitted. Where it is stated that natural ventilation is required, this may be supplemented but not replaced by a mechanical supply system or a mechanical ventilating system, or both.
The air supply for every ventilating system, either natural or mechanical, shall be
taken directly from out-of-doors, except that:
(a) When air is supplies by a mechanical ventilating supply system, a portion of the code
required air supply may be recirculated, provided the system is equipped with such devices
for control of temperature, and dust content in the spaces to be ventilated and that the
condition of the air so supplied, (except as to temperature) are substantially the same as
though all of the supply air were taken from out-of-doors. The portion or volume of air so
recirculated may be considered as exhaust from the room from which it is withdrawn. Under
such conditions, not less than 33 and one-third percent of the code requirements shall be
taken from out-of-doors by the mechanical ventilating supply system; and 66 and two-thirds
percent of the code requirements may be recirculated air, plus any additional air volume
of system design capacity in excess of code requirements.
(c) The intake drawing air from out-of-doors shall be at such a point that the air supply
will be uncontaminated and that the openings will be unobstructed at all times. The intake
opening shall be not less than 15 feet from the discharge outlet of any exhaust fan.
(d) No air exhausted from bath, toilet, urinal, or similar room, lavatory, locker, coat
room, kitchen, boiler room, or rooms of similar use in which such air may be contaminated
by smoke, gases, or dust which might be noxious, dangerous, or detrimental to health shall
be recirculated at any time; except that air exhausted from locker and coat rooms or
kitchens may be recirculated when unoccupied.
Mechanical exhaust systems for bath, toilet, urinal, locker, service sink toilet
closets, and similar rooms shall be independant of other mechanical exhaust systems,
except when all of the following conditions exist simultaneously:
(a) The total air exhausted from said bath, toilet, urinal locker, service sink or similar
rooms shall not exceed 10 percent of the capacity of the fan;
(b) No air from such exhaust systems shall be recirculated at any time;
(c) The exhaust fan shall be in operation at all times the building is occupied;
(d) No room or space in which food is prepared or consumed shall be connected to the
common exhaust system.
Every ventilation system, either natural or mechanical, shall be kept in good repair and in operation so as to insure the required ventilation of all rooms and spaces to be ventilated thereby during all hours of human occupancy. No ventilating system shall be operated so as to cause objectional drafts upon the occupants.
| 13-176-070 - Tables of ventilation requirements | |||
|---|---|---|---|
| Room Purpose | Conditions Area of ventilation openings in percentage of floor area. |
Requirements Minimum CFM supply or exhaust per square foot of floor area, except as otherwise noted. |
Other conditions |
| Classrooms | Supply 1.5 CFM and Exhaust 0.75 CPM or Supply 1.5 CPM and Relief Opening. | ||
| Auditorium | Supply 3.0 CFM and exhaust 1.5 CFM in open spaces having no fixed seats plus supply 30 CFM, and exhaust 30 CFM, for each fixed seat. | Capacity 601 or more persons | |
| Auditorium | Not less than 5 | Supply 3.0 in open spaces having no fixed seats plus supply 30 for each fixed seat and relief opening. | Capacity 600 or less persons |
| Auditorium | Less than 5 | Supply 3.0 CFM and exhaust 1.5 CFM in open spaces having no fixed seats plus supply 30 CFM, and exhaust 30 CFM, for each fixed seat. | Capacity 600 or less persons |
| Gymnasiums | Less than 5 | Supply .8 CFM to which the following shall be added if seats are provided for spectators. Supply 2.0 CFM and exhaust 1.0 CFM or supply 2.0 and refief opening in open spaces having no fixed seats plus supply 20 CFM for each fixed seat. | |
| Gymnasiums | Not less than 5 | No requirements | |